Description
Description
Specification | Details |
---|---|
Catalog Number | 1756-IA8D |
Module Type | ControlLogix 8-Point Diagnostic Digital AC Input Module |
Number of Inputs | 8 (4 points/group) |
Operating Voltage Range | 79…132V AC, 47…63 Hz |
Input Delay Time | Off to On: Hardware delay: 10 ms max + user-selectable filter time (1 ms or 2 ms); On to Off: Hardware delay: 8 ms max + user-selectable filter time (9 ms or 18 ms) |
Current Draw @ 5.1V | 100 mA |
Current Draw @ 24V | 3 mA |
Total Backplane Power | 0.58 W |
Power Dissipation (Max) | 4.5 W @ 60 °C (140 °F) |
Isolation Voltage | 125V continuous between groups of 4 inputs |
Operating Temperature | 0 to 60 °C (32 to 140 °F) |
Storage Temperature | -40 to 85 °C (-40 to 185 °F) |
Relative Humidity | 5% to 95% non-condensing |
Certifications | CE, c-UL-us, RCM |